microSpider IndustrialThe microSpider2 Industrial is a complete data logging and telemetry system. It includes all software, hardware, backup battery and a built-in mobile phone module. The enclosure fits standard DIN rail brackets.

The microSpider2 Industrial can

  • monitor inputs (analogue, digital, counters, frequency, quadrature/shaft encoder)
  • control outputs
  • generate SMS, email and twitter alarms
  • record data
  • send data via e-mail, FTP and HTTP
  • communicate via internal 3G/4G modem
  • charge an external SLA battery via a built-in solar panel / mains charger
  • update software automatically in-field from remote servers, or update from connected pc.

The microSpider2 Industrial is ideal for long term monitoring and can interface with a wide range of sensors and meters. the browser interface makes it easy to set up and test. It can be powered from 12v dc.

The microSpider2 Industrial logs data and automatically sends reports via email or ftp. Any alarms can activate outputs, send SMS and email alarm messages as well as historical reports

Economical – low upfront, installation and operational costs

Easy to use – simple familiar web browser interface

Easy to install

Integrated mounting – DIN rail compatible.

Simply connect antenna, battery / supply and inputs.

No special software required

setup and download using browser

can be managed remotely (requires LiveSMS option)

reports sent straight to your PC or server

text/csv reports open in Excel

receive reports via email, FTP and HTTP

No licenses, royalties or service agreements

Large internal memory – full local backup of data

Physical

Dimensions: (approx) 156(L) x 60(H) x 87 (W) mm

Weight: (approx) 500 g

Operating temperature: -5 to +50 degrees Celsius

Data Recorder

Capacity: approximately 400,000 records

Storage memory: Non-volatile FLASH

Time resolution: 1 second

Download format: CSV file

Power Supply

Operating voltage:

Nominal 12V DC, min 1A

Power consumption:

Standby 65 uA
Active <3mA (modem off, LAN powered externally)
Active 100mA (modem on, LAN powered internally)
Active 250mA (modem on, communicating)

Integrated battery charger regulator:

Charges an external 12V SLA battery from an external 12V solar panel or a 16 - 30V DC 2A
power source

Backup battery:

Internal, user replaceable 9V battery (optional)

Warranty

Factory backup 12 months parts and labour guarantee

Inputs

Number of inputs:

  • Up to 4 digital
  • Up to 4 analog
  • 4 system inputs
  • Up to 20 SDI-12 / Modbus (with optional SDI-12/Modbus Interface)

Digital Inputs:

  • 0 - 12V DC Voltage or voltage-free switch contact
  • Can be used as switch, event (rainfall), counter or utility meter inputs (user selectable)

Analogue Inputs: Resolution 12 bits

  • 4 - 20 mA, common ground
  • 0 - 2.4V, common ground
  • 0 - 5V, common ground
  • 0 - 10V, common ground

Counter / Event Inputs

  • Minimum pulse width: 5 ms
  • Maximum frequency: 100 Hz
  • Range: 0 - 999,999

System Inputs:

  • System temperature
  • External battery voltage
  • Charger voltage
  • LAN power voltage

Outputs

Number of outputs 3 

  • 1 x Switched power for sensor power / control
  • 1 x Open collector for accessory control
  • 1 x Low power sensor supply (3.3V or 5V)

Alarms

Number of alarms: 16

Type: SMS, twitter and/or e-mail transmission

Trigger: User definable input and trigger point

SMS / e-mail / twitter text: 1 per alarm, user definable

Number of phone numbers: 3 per alarm, user definable

Number of e-mail addresses 2 per alarm, user definable

Communication Interfaces

Ethernet 10/100 base-T, RJ-45 connector

Cellular phone module: Built-in 4G, 3G or Iridium satellite

Antenna: internal antenna - External antenna, SMA connector

Internet connectivity: 4G, 3G, LAN

Product is available in a variety of configurations to suit your needs, you may specify any of the following:

  • 4G/3G or Iridium satellite communications
  • Live SMS
    Provides remote access from a web browser or mobile phone and extends the SMS capabilities of the microSpider2. Features include alarm acknowlegement, control activation and the ability to schedule modem power ups to create communication windows.
  • DNP3
    Compliant with Level 2 of the DNP3 standard, supporting all of the microSpider2's inputs and controls, the DNP3 option allows the microSpider2 to communicate with a SCADA system via 4G/3G modem or local area network.

Accessories


Weatherproof enclosure

SDI-12/Modbus Interface

GPS Interface

Mains power supply

Solar panel

Sealed lead acid battery

Range of external 4G/3G Antennae

Software

microSpider2 Industrial Software v1.95 (Zip File)

Manuals / Brochures

microSpider2 Industrial Brochure

microSpider2 Industrial Quick Start Guide

microSpider2 Manual V1.26

DNP3

microSpider2 Device Profile

microSpider2 XML Device Profile (Zip file)

 

News

February 2013

Responding to requests from its customers, Halytech has improved its Illuminator sportsfield lighting management system to monitors energy use and, where appropriate, enable councils to charge for it.

Read more ...

Contact Us

Unit 11, 22 Lexington Drive
Norwest Business Park
Bella Vista NSW 2153

9:00 - 5:00 Monday to Friday

phone +61 2 8814 5235

This email address is being protected from spambots. You need JavaScript enabled to view it.

This email address is being protected from spambots. You need JavaScript enabled to view it.